Services

Maintenance and routine repairs of diesel generator sets (gensets)

Diesel generator sets from 10 kW: scheduled maintenance and repairs on request. A certificate of completed works after every visit.

Kyiv and Kyiv region, all of Ukrainedispatch from 3 hours6 field crews12 service specialistsunder contractvia Prozorro (Ukraine's public e-procurement system)

Call +380 50 102 99 99Hours Mon–Fri 09:00–17:00 (Kyiv time)

Procurement documents

3 hours is the minimum time. The actual time depends on the region and the site.

Scope of work

What is included

Lubrication system
Engine oil and oil filter replacement, oil level and pressure check.
Fuel system
Fuel filter replacement, check of tank mounting and fuel line connections, check for water in the pre-filter.
Air system
Air filter cleaning and replacement, check of the crankcase ventilation system.
Cooling system
Check of the radiator, belts and pulleys, coolant replacement, heater check.
Batteries and charging
Voltage, state of charge, internal resistance, cranking voltage; check of the charger, starter and charging alternator.
Controls and protections
Start on command from the control cabinet, check of temperature and oil pressure protections, control relay and power breaker contacts.
Mechanical components
Inspection of engine and alternator mounts, coupling, exhaust system, bolted joints and clamps.
Defect report listing required works and materials.

On request

Electrical measurements
Grounding loop resistance; inspection of winding connections, busbars and alternator grounding.
Emission measurements
Exhaust gas composition under load.
ATS
Testing and adjustment of the automatic transfer switch.

After every visit

Documents after the works

Certificate of completed works with recommendations — the primary document issued after every visit or stage

On request: maintenance reports for lubrication, fuel and air systems; battery and charger test report; maintenance report for protections and control circuits; report on the condition of moving and fixed joints; grounding resistance test report; exhaust gas measurement report; engine oil certificate.

Maintenance or repair request: +380 50 102 99 99

Diagram

Maintenance scope by genset component

  • Enginestandard maintenanceLubrication, fuel, air and cooling systems; exhaust system, bolted joints and clamps.
  • Generator (alternator)standard maintenanceInspection of engine and alternator mounts, coupling.On request: winding connections, busbars, alternator grounding.
  • Battery and chargingstandard maintenanceStarter battery and charger: voltage, state of charge, internal resistance; starter, charging alternator.
  • Control cabinetstandard maintenanceStart on command; temperature and oil pressure protections; control relay and power breaker contacts.
  • ATSon requestTesting and adjustment of the automatic transfer switch (ATS).
  • Grid
  • Site loads

Not tied to a component

  • Defect report listing required works and materialsstandard maintenance
  • Emission measurements: exhaust gas composition under loadon request
  • standard maintenance
  • on request
  • context, no works
  • power circuit, start
  • control
Diagram · Maintenance scope by genset component

Work intervals

Maintenance schedule

Indicative intervals. Specific engine hours and intervals are set by the unit manufacturer's schedule.
WorkIntervalNote
Inspection without start-up, fluid levels, leaksweeklyvisual inspection
Test run without load / with loadmonthly, at least 30 min at ~30% of rated powerif required at the site
Battery condition, terminals, chargermonthly; load test annuallybattery replacement based on results
Engine oil and oil filterper the manufacturer's schedule (engine hours) or at least 1× per yeartypically 250 engine hours / 6 months
Fuel filterper the manufacturer's schedule or annuallydepends on fuel cleanliness
Air filterby clogging indicator, at least annually
Coolantannual check, replacement per schedule (1–3 years)
Drive belts, hoses, mounts, jointsmonthly inspection, retightening every six months
Protections and controlsevery six months to a yearATS on request

What we work with

Equipment

Design type
  • Open
  • Canopy-enclosed
  • Containerized
  • Trailer-mounted mobile
Rated power
from 10 kW

Manufacturers

Gensets
SDMO · FG Wilson · Malcomson · AKSA · Teksan · Genesal Energy · Pramac · Himoinsa · Kohler · Caterpillar
Engines
Cummins · Perkins · Volvo Penta · MTU · Deutz · Doosan · Baudouin · Yanmar · Mitsubishi · Iveco/FPT

The list of manufacturers is not a list of authorized service centers.

Contacts

Get in touch

Hours
Mon–Fri 09:00–17:00 (Kyiv time)
Address
16 Stepana Bandery Ave., Kyiv 04073, Ukraine